Find a distributor > >
Skip Navigation LinksHome > Products > Gas-Driven VRF > ECO GW-Multi
Product Selector

Gas Driven VRF

An ECO GW-Multi Unit
  • Diversity ratio 50% - 200%
  • Extended pipe runs (total 780m)
  • Equivalent sound levels to electric VRF systems
  • Silent mode offers a further 2dB(A) reduction
  • Chiller option
    • 9HP (25kW cooling - 30kW heating)
    • 18HP (50kW cooling - 60kW heating)
  • 10,000 run hours between engine service intervals
    (equivalent to one maintenance every 3.2 years*)
  • Connectability of up to 32 indoor units
  • Full heating capacity down to -20°C
  • No defrost cycle

* Assuming 3120 running hrs per year - 12 hrs x 5 days x 52 weeks

Hot water supply function (during cooling operation only)

SGP-E120K1GU2W - SGP-E150K1GU2W - SGP-E190K1GU2W - SGP-E240K1GU2W

System advantage

The engine waste heat, which is normally exhausted into the atmosphere, is recovered via the heat exchanger and effectively used as hot water, so the GHP chiller acts as a sub system that alleviates the load on the client's main hot water system and therefore offers ‘free’ hot water.

Water heating capacity 22kW (of 75°C hot water)
Hot water piping allowable pressure 0.7 MPa
Hot water circulation rate 2.1 - 3.9m3/h
Hot water pipe size 3/4 inch

 

An ECO GW-Multi Unit
HP 8 10 13 16 20 25
Model name SGP-E70K1GU2 SGP-E90K1GU2 SGP-E120K1GU2W SGP-E150K1GU2W SGP-E190K1GU2W SGP-E240K1GU2W
Cooling capacity kW 22.40 28.00 35.50 45.00 56.00 71.00
Heating capacity kW 25.00 31.50 40.00 50.00 63.00 80.00
Hot water capacity kW - - 13.00 16.00 17.00 27.00
EER / COP Cooling 1.35 1.37 1.39 1.41 1.60 1.27
Heating 1.41 1.45 1.40 1.45 1.50 1.33
Electric rating Cooling kW 0.55 0.96 1.13 1.60
Heating kW 0.58 1.06 1.24 1.70
Gas Consumption C kW 16.1 20.4 24.5 32.0 33.9 54.5
H-STD kW 17.2 21.7 27.5 34.5 40.9 58.6
Dimensions (H/W/D) mm 2,253/1,290/1,000(+106) 2,253/1,735/1,000(+106)
Weight kg 640 660 920 950 980
Starting Current A 25 30
Fan Motor Power kW 0.45×1 0.45×2
Pipe Suction Inches 7/8 1 1/8 1 1/8 1 3/8
Liquid Inches 1/2 5/8 3/4
Fuel gas Inches 3/4(Male screw)
Operating Sound dB(A) 56 56 57 58 60
Maximum number of indoor units 20 24 24 24 28 32

* Values were obtained with the outdoor unit operator standing 1m in front of the unit and operator height of 1.5m. Gas consumption indicates calorifi c value of 40MJ/NM3 +_ 5%